МГП FS FireStop ECO module construction
- Cylinder
- Siphon tube
- Discharge valve
- Pressure indicator / gauge
- Safety device
- High-pressure hose (РВД)
- Discharge nozzle
- Electromagnetic or pneumatic actuator with manual release
- Wall bracket
- Piping

Actuator types
Electromagnetic actuator with manual release
Voltage: 24 ± 2 V; current: 1–1.5 A. Maximum actuation delay: 2 s.
Pneumatic actuator with manual release
The pneumatic actuator version is selected according to the system layout.
Construction of cylindrical modules in a cylinder bank
- Electrical actuator
- Pneumatic actuator
- Pneumatic actuation hose
- High-pressure hose
- Manifold
- Check valve
- Safety valve
- Module rack
- Pneumatic actuation blanking plug

Equipment documentation
Scope of supply
| Item | Supply |
|---|---|
| Module: cylinder, siphon tube, discharge valve, pressure gauge and safety device | Included |
| Operating manual with module datasheet | Included |
| Actuator with manual release | Separate |
| Brackets / clamps | Separate |
| High-pressure hose (РВД) | Separate |
| Discharge device / nozzle | Separate |
| Piping | Separate |

Operating principle and layout of a floor-mounted gaseous fire suppression system
- Floor-mounted FireStop module
- Smoke or heat fire detectors
- R3-Рубеж-2ОП addressable control panel
- Illuminated warning signs
- Manual release device
- Sounder
- МПТ-1 addressable module
- Module bracket / rack
- Distribution piping
- ИВЭПР — secondary power supply
- R3-ПДУ-ПТ multi-room control device

Fire detection
Addressable detectors (2) send signals to the R3-Рубеж-2ОП panel (3). Once the release conditions specified in the design and system settings are met, the panel sends a command over the addressable loop to the МПТ-1 suppression control module (7).
Warning and release delay
МПТ-1 activates the connected warning signs (4) and sounders (6), then counts down the configured gas release delay. The sequence accounts for the automatic operating mode and design interlocks, including door monitoring.
Suppression release
When the delay ends and release conditions are met, МПТ-1 (7) signals the actuator on the floor-mounted module (1). The agent flows through the piping (9) to the discharge nozzles.
Suppression and status monitoring
The gas spreads throughout the protected volume, establishing the extinguishing concentration. With the appropriate sensors connected, МПТ-1 monitors discharge using mass or pressure signals and reports events to the panel. System status and faults are displayed on R3-Рубеж-2ОП.
Benefits of floor-mounted module systems
«FireStop ECO»
Fire alarm integration
Compatible with systems from Рубеж, Bolid, Стрелец and other manufacturers
Lower operating costs
Cylinder inspection every 10 years reduces module maintenance costs
Precise sizing to match the calculation
Cylinders from 16 to 180 L allow precise module selection without paying for excess gas
Recommended for protecting these facilities
Data centres and server rooms
Power stations and energy facilities
Bank vaults
Art galleries, museums and libraries
Electrical switchgear rooms and diesel generator sets
Modular containers
Document archives
How to order
Step 1 / Initial enquiry
Request a callback or contact us by phone or email
Step 2 / Consultation
We answer your questions and explain our products, model differences, applications, ordering and delivery terms
Step 3 / Calculation and equipment selection
Using your answers, our technical team calculates the required number of modules and selects the extinguishing agent
Step 4 / Quotation
Based on the calculation, our sales team prepares a quotation detailing equipment, delivery times, prices and special terms
Step 5 / Contract
Once all terms are agreed, we sign the contract
Step 6 / Dispatch and delivery
After receiving payment under the contract, we manufacture and dispatch the products and monitor delivery

Module datasheet
Cylinder datasheet
EAC certificate
EAC certificate